Wire Size by Current Draw of Total Load - Best practice never exceed 80% of rating.
i.e: Draw is 15 amps, use 20 amp circuit.
Note: wire run over 300ft,consider voltage drop.
Use no aluminum wire to wire receptacles, switches or appliances.
Wire Size / AWG.Aluminum Wire Max CurrentCopper Wire Max Current
0000 gauge200 amps253 amps
000 gauge175 amps214 amps
00 gauge150 amps186 amps
0 gauge125 amps163 amps
2 gauge100 amps119 amps
4 gauge60 amps89 amps
6 gauge40 amps65 amps
8 gaugeN/A48 amps
10 gaugeN/A30 amps
12 gaugeN/A20 amps
14 gaugeN/A15 amps

Conductor Sizes for Service Feeders - 120/240v,3 Wire,Single-Phase home.
CopperAluminumService Amps
4g2g100
3g1g110
2g1/0125
1g2/0150
1/03/0175
2/04/0200
3/0250225
4/0300250
250350300
350500350
400600400
Check local and National Electrical Code regulations or contact a qualified electrician.
Basic wire sizing guide for US 120 and 240 volts
# = American Wire Gauge (AWG), the lower the number the larger the wire guage.
'Service cable' is usually single #4 wire and up).

Typically 15-30 amp can safely handle 95% to 100% of it's max rating for an hour.
Known safe capacity (NEC) for 100% 'on' time circuits is 80% of load. (air conditioner,ballasts)

Basic sheathed xx/2 and xx/3 cable available 6 gauge.
Usually insulated" #8 + wire is stranded (Service cable).
#4 and above = Cable
1/0 and 2/0 are Service cable
Larger than #8 or #6 ,buy 'service type' cable. 2 problems on long runs :high cost , cable may not fit appropriately-sized breaker. Put ballast on 240V when 2400+ watts of lightpower on single circuit.

120V (US) (@ 80% max load) - (50ft run or less)
Gauge Amps Watts
#16 9 1080
#14 12 1440
#12 16 1920
#10 24 2880
#8 32 3840
#6 40 4800
#4 48 5760

240V (US) (@ 80% max load) - (50ft run or less)
Gauge Amps Watts
#16 9 2160
#14 12 2880
#12 16 3840
#10 24 5760
#8 32 7680
#6 40 9600
#4 48 11520