WIRE GAUGE
 AMPS 14 12 10 8 6 4 2 1 0 00 000 0000
1 213 338 537 854 1359 2160 3434 4332 5460 6887 8684 10951
2 106 169 269 427 679 1080 1717 2166 2730 3444 4342 5475
4 53 85 134 214 340 540 859 1083 1365 1722 2171 2738
6 35 56 90 142 226 360 572 722 910 1148 1447 1825
8 27 42 67 107 170 270 429 542 682 861 1086 1369
10 21 34 54 85 136 216 343 433 546 689 868 1095
15 14 23 36 57 91 144 229 289 364 459 579 730
20 17 27 43 68 108 172 217 273 344 434 548
25 21 34 54 86 137 173 218 275 347 438
30 18 28 45 72 114 144 182 230 289 365
35 24 39 62 98 124 156 197 248 313
40 34 54 86 108 136 172 217 274
45 30 48 76 96 121 153 193 243
50 27 43 69 87 109 138 174 219
Wire Sizing Chart 24 Volt System
Maximum one-way distance (feet) for 5% voltage loss in 24 volt systems. Wire Size (AWG) Wire Sizing Chart 12 Volt System
Maximum one-way distance, in feet of two conductor copper wire for 5% voltage loss in 12 volt systems. Wire Size (AWG)
May double distance if 4% loss is ok.
Never exceed 2% drop for wire connecting PV modules and batteries.
Usually 4-5% loss ok for connecting batteries and lighting circuits.
Multiply distances by 2 for 24 volts and by 4 for 48 volts.